Magnetic properties of silicon iron electrical steel are determined by using standardized measurement setups and distinct excitation parameters. Characteristic values for magnetic loss and magnetization are used to select the most appropriate material for its application. This approach is not sufficient, because of the complex material behavior inside electrical machines, which can result in possible discrepancies between estimated and actual machine behavior. The materials’ anisotropy can be one of the problems why simulation and measurement are not in good accordance.With the help of a rotational single sheet tester, the magnetic material can be tested under application relevant field distribution. Thereby, additional effects of hysteresis and anisotropy can be characterized for detailed modelling and simulation.
As for a single line-to-ground fault in an ungrounded distribution system, the power-frequency current is too low to detect the fault. The transient current is more palpable than that at a power-frequency of 50 or 60 Hz. It is an effective method to estimate the fault using the transient fault current. To analyze and calculate the transient current of single line-to-ground faults, an equivalent circuit is proposed in this paper. This model is based on distributed parameters of power lines. And it contains positive, negative and zero sequence information. The transient equivalent circuit consists of equivalent resistance, equivalent inductance and equivalent capacitance. And the method of calculation the equivalent ele- ments is also submitted.MATLAB simulation results showthat the newtransient equivalent circuit has higher accuracy and stronger adaptability compared with the traditional one.